Product ID: 12518OP3GFP405TC-W40

12518OP3GFP405TC-W40 WEG 125HP Fire Pump Electric Motor, 1800RPM

MFG: WEG Electric Corporation
MFG Part Number: 12518OP3GFP405TC-W40

Selected accessories will also be added to cart
$4,988.25 / Each
Quantity:
IC01 - ODP, IP23 Frame, 404TC/405TC Frame, 460/380VAC 50/60Hz 3 Phase, 14282560, High Efficiency, Foot Mounted, Cast Iron Frame, 2-7/8" Keyed Shaft

Electric Motors

Frame 404/5TC
Output 125 HP
Number of Poles 4
Frequency 60 Hz
Rated speed 1775 rpm
Slip 1.39 %
Rated voltage 460 V
Rated current 139 A
L. R. Amperes 904 A
LRC 6.5x(Code G)
No load current 38.0 A
Rated torque 370 ft.lb
Locked rotor torque 210 %
Breakdown torque 229 %
Locked rotor time 21s (cold) 12s (hot)
Moment of inertia (J) 21.5 sq.ft.lb
Design B
Insulation Class F
Service factor 1.15
Temperature rise 80 K
Duty Cycle Cont.(S1)
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP23
Enclosure IC01 - ODP
Mounting F-1
Rotation¹ Both (CW and CCW)
Approx. weight³ 1016 lb
(1) Looking the motor from the shaft end.; (3) Approximate weight, subject to be changed after manufacturing process.; (4) At 100% of full load.

Efficiency

50% 75% 100%
94.1  94.5  94.5 

Power factor

50% 75% 100%
0.76  0.84  0.86 
Frame 404/5TC
Output 125 HP
Number of Poles 4
Frequency 50 Hz
Rated speed 1465 rpm
Slip 2.33 %
Rated voltage 380 V
Rated current 170 A
L. R. Amperes 833 A
LRC 4.9x(Code D)
No load current 37.0 A
Rated torque 448 ft.lb
Locked rotor torque 180 %
Breakdown torque 200 %
Locked rotor time 19s (cold) 11s (hot)
Moment of inertia (J) 21.5 sq.ft.lb
Design B
Insulation Class F
Service factor 1.00
Temperature rise 105 K
Duty Cycle Cont.(S1)
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP23
Enclosure IC01 - ODP
Mounting F-1
Rotation¹ Both (CW and CCW)
Approx. weight³ 1016 lb
(1) Looking the motor from the shaft end.; (3) Approximate weight, subject to be changed after manufacturing process.; (4) At 100% of full load.

Efficiency

50% 75% 100%
91.7  92.4  92.4 

Power factor

50% 75% 100%
0.81  0.85  0.87 
Frame 404/5TC
Output 125 HP
Number of Poles 4
Frequency 50 Hz
Rated speed 1470 rpm
Slip 2.00 %
Rated voltage 400 V
Rated current 162 A
L. R. Amperes 907 A
LRC 5.6x(Code F)
No load current 40.0 A
Rated torque 447 ft.lb
Locked rotor torque 190 %
Breakdown torque 200 %
Locked rotor time 18s (cold) 10s (hot)
Moment of inertia (J) 21.5 sq.ft.lb
Design B
Insulation Class F
Service factor 1.00
Temperature rise 105 K
Duty Cycle Cont.(S1)
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP23
Enclosure IC01 - ODP
Mounting F-1
Rotation¹ Both (CW and CCW)
Approx. weight³ 1016 lb
(1) Looking the motor from the shaft end.; (3) Approximate weight, subject to be changed after manufacturing process.; (4) At 100% of full load.

Efficiency

50% 75% 100%
92.4  93.0  93.0 

Power factor

50% 75% 100%
0.80  0.84  0.86 
Frame 404/5TC
Output 125 HP
Number of Poles 4
Frequency 50 Hz
Rated speed 1470 rpm
Slip 2.00 %
Rated voltage 415 V
Rated current 157 A
L. R. Amperes 926 A
LRC 5.9x(Code F)
No load current 42.0 A
Rated torque 447 ft.lb
Locked rotor torque 210 %
Breakdown torque 229 %
Locked rotor time 19s (cold) 11s (hot)
Moment of inertia (J) 21.5 sq.ft.lb
Design B
Insulation Class F
Service factor 1.00
Temperature rise 105 K
Duty Cycle Cont.(S1)
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP23
Enclosure IC01 - ODP
Mounting F-1
Rotation¹ Both (CW and CCW)
Approx. weight³ 1016 lb
(1) Looking the motor from the shaft end.; (3) Approximate weight, subject to be changed after manufacturing process.; (4) At 100% of full load.

Efficiency

50% 75% 100%
93.0  93.6  93.6 

Power factor

50% 75% 100%
0.78  0.83  0.85 

Features

Frame Material Cast Iron 
Impregnation Method Constant Resin Flow 
Regreasing System At Drive end and Non-drive end 
Main terminal box hole NPT 3" 
Terminal Block Without 
Shaft Locking Device Without 
Shaft Material SAE 1040/45 Carbon Steel 
Painting RAL 3002 203A (ISO 12944 - C2) 
Grounding Lugs Double 
Fan Cover material Without Fan Cover 
Tropicalized Painting Without 
Fan material Without fan 
Bearing cap Yes- Bearing Cap 
Bolt Material Carbon Steel 
Balancing Method 1/2 Key 
Drip Cover Without 
Overload protector (phenolic) Without overload protector  
Connection Cables Quantity 12