General Specifications
Environmental
Enclosure UL Open Type (IP20/IP00), Optional UL Type 1
Ambient Temperature "+14 to +122°F (-10 to +50°C) - UL Open Type
+14 to +104°F (-10 to +40°C) - UL Type 1"
Storage Temperature -13 to +149°F (-25 to +65° C)
Humidity 5% to 95% With No Condensation
Altitude 0 to 3,300 ft. (1,000 m) Without Derating, Derate Output Current for Higher Altitudes per User's Manual
Codes and Standards
UL508C, C22.2 No.14, EN61800-5-1:2007
Electrical
Input Voltage: Range(Hz) - Phase "200-240VAC(50/60Hz) - 3Ph (<30Hp)
200-220VAC(50Hz), 200-230VAC(60Hz) - 3Ph (>40Hp)
380-480VAC(50/60Hz) - 3Ph (<40Hp[LD])
380-440VAC(50Hz), 380-480VAC(60Hz) - 3Ph (>50Hp[LD])"
Input Voltage: Tolerance, Unbalance 3-Ph Input = +10% to -15%, <2%
Input Frequency: Nominal, Tolerance 50/60Hz, +/-5%
Displacement Power Factor >0.98 (@ Rated Load)
Output Voltage: Range-Phase 0 to Maximum Input Voltage-3Ph
Maximum Output Frequency 120Hz
Motor Control Method V/f
Overload Capacity 120% Rated Current for 1 min.
Analog Inputs "Qty 2: 0 to +10VDC
Qty 1: 4 to 20mA"
Digital Inputs Qty 7: Programmable Inputs
Analog Outputs "Qty 1: Configurable for 0 to +10VDC or 4 to 20mA, User Selectable for Proportional Analog Signal Functionality
Qty 1: 4 to 20mA, User Selectable for Proportional Analog Signal Functionality"
Digital Outputs "Qty 1: Form C (1N.O. & 1N.C.) Dry Contacts Rated 0.3A @ 230VAC Max, User Selectable Functionality
Qty 1: Form A (1N.O.) Dry Contact Rated 0.3A @ 230VAC Max, User Selectable Functionality
Qty 3: Transistor Output Rated 50mA @ 27Vdc Max, User Selectable Functionality"
Power Supply Qty 1: 24VDC, 50mA Max