We are now required to collect sales tax in Florida, Iowa, New Jersey & Ohio. If you are tax exempt, please create an account and send us your sales tax exemption form before placing an order. MORE INFO
/Products/Electric Motors/3 Phase/WEG/Air Handling/Cooling Tower/02518AT3ECT284T-W22 WEG 25HP Cooling Tower Electric Motor, 1800RPM

Product ID: 02518AT3ECT284T-W22

02518AT3ECT284T-W22 WEG 25HP Cooling Tower Electric Motor, 1800RPM

MFG: WEG Electric Corporation
MFG Part Number: 02518AT3ECT284T-W22

Selected accessories will also be added to cart
$2,499.75 / Each
Quantity:
IC410 - TEAO, IP55, 284T Frame, 208-230/460/380VAC 50/60Hz 3 Phase, 12126282, NEMA Premium Efficiency, Foot Mounted, Cast Iron Frame, 1-7/8" Keyed Shaft

Electric Motors

Frame 284T
Output 25 HP (18.5 kW)
Number of Poles 4
Frequency 60 Hz
Rated speed 1770 rpm
Slip 1.67 %
Rated voltage 208-230/460 V
Rated current 65.2-59.0/29.5 A
L. R. Amperes 404-366/183 A
LRC 6.2x(Code G)
No load current 19.0-22.0/11.0 A
Rated torque 74.2 ft.lb
Locked rotor torque 240 %
Breakdown torque 270 %
Locked rotor time 43s (cold) 24s (hot)
Moment of inertia (J) 5.11 sq.ft.lb
Design B
Insulation Class F
Service factor 1.25
Temperature rise 80 K
Duty Cycle Cont.(S1)
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP55
Enclosure IC410 - TEAO
Mounting F-2
Rotation¹ Both (CW and CCW)
Noise level² 63.0 dB(A)
Approx. weight³ 375 lb
(1) Looking the motor from the shaft end.; (2) Measured at 1m and with tolerance of +3dB(A).; (3) Approximate weight, subject to be changed after manufacturing process.; (4) At 100% of full load.

Efficiency

50% 75% 100%
92.4  93.0  93.6 

Power factor

50% 75% 100%
0.70  0.80  0.84 
Frame 284T
Output 20 HP (15 kW)
Number of Poles 4
Frequency 50 Hz
Rated speed 1470 rpm
Slip 2.00 %
Rated voltage 380 V
Rated current 29.1 A
L. R. Amperes 175 A
LRC 6.0x(Code G)
No load current 11.0 A
Rated torque 71.4 ft.lb
Locked rotor torque 229 %
Breakdown torque 260 %
Locked rotor time 32s (cold) 18s (hot)
Moment of inertia (J) 5.11 sq.ft.lb
Design B
Insulation Class F
Service factor 1.00
Temperature rise 80 K
Duty Cycle Cont.(S1)
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP55
Enclosure IC410 - TEAO
Mounting F-2
Rotation¹ Both (CW and CCW)
Noise level² 61.0 dB(A)
Approx. weight³ 375 lb
(1) Looking the motor from the shaft end.; (2) Measured at 1m and with tolerance of +3dB(A).; (3) Approximate weight, subject to be changed after manufacturing process.; (4) At 100% of full load.

Efficiency

50% 75% 100%
91.3  92.1  92.1 

Power factor

50% 75% 100%
0.69  0.80  0.85 
Frame 284T
Output 20 HP (15 kW)
Number of Poles 4
Frequency 50 Hz
Rated speed 1473 rpm
Slip 1.80 %
Rated voltage 400 V
Rated current 28.2 A
L. R. Amperes 189 A
LRC 6.7x(Code H)
No load current 11.7 A
Rated torque 71.3 ft.lb
Locked rotor torque 250 %
Breakdown torque 300 %
Locked rotor time 32s (cold) 18s (hot)
Moment of inertia (J) 5.11 sq.ft.lb
Design B
Insulation Class F
Service factor 1.00
Temperature rise 80 K
Duty Cycle Cont.(S1)
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP55
Enclosure IC410 - TEAO
Mounting F-2
Rotation¹ Both (CW and CCW)
Noise level² 61.0 dB(A)
Approx. weight³ 375 lb
(1) Looking the motor from the shaft end.; (2) Measured at 1m and with tolerance of +3dB(A).; (3) Approximate weight, subject to be changed after manufacturing process.; (4) At 100% of full load.

Efficiency

50% 75% 100%
91.3  92.5  92.6 

Power factor

50% 75% 100%
0.65  0.78  0.83 
Frame 284T
Output 20 HP (15 kW)
Number of Poles 4
Frequency 50 Hz
Rated speed 1475 rpm
Slip 1.67 %
Rated voltage 415 V
Rated current 27.5 A
L. R. Amperes 198 A
LRC 7.2x(Code J)
No load current 12.4 A
Rated torque 71.2 ft.lb
Locked rotor torque 270 %
Breakdown torque 330 %
Locked rotor time 32s (cold) 18s (hot)
Moment of inertia (J) 5.11 sq.ft.lb
Design B
Insulation Class F
Service factor 1.00
Temperature rise 80 K
Duty Cycle Cont.(S1)
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP55
Enclosure IC410 - TEAO
Mounting F-2
Rotation¹ Both (CW and CCW)
Noise level² 61.0 dB(A)
Approx. weight³ 375 lb
(1) Looking the motor from the shaft end.; (2) Measured at 1m and with tolerance of +3dB(A).; (3) Approximate weight, subject to be changed after manufacturing process.; (4) At 100% of full load.

Efficiency

50% 75% 100%
91.2  92.5  92.7 

Power factor

50% 75% 100%
0.62  0.75  0.82 
Frame 284T
Output 25 HP (18.5 kW)
Number of Poles 4
Frequency 50 Hz
Rated speed 1455 rpm
Slip 3.00 %
Rated voltage 380 V
Rated current 35.9 A
L. R. Amperes 190 A
LRC 5.3x(Code F)
No load current 11.0 A
Rated torque 90.2 ft.lb
Locked rotor torque 180 %
Breakdown torque 210 %
Locked rotor time 25s (cold) 14s (hot)
Moment of inertia (J) 5.11 sq.ft.lb
Design B
Insulation Class F
Service factor 1.00
Temperature rise 105 K
Duty Cycle Cont.(S1)
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP55
Enclosure IC410 - TEAO
Mounting F-2
Rotation¹ Both (CW and CCW)
Noise level² 61.0 dB(A)
Approx. weight³ 375 lb
(1) Looking the motor from the shaft end.; (2) Measured at 1m and with tolerance of +3dB(A).; (3) Approximate weight, subject to be changed after manufacturing process.; (4) At 100% of full load.

Efficiency

50% 75% 100%
92.4  91.7  91.0 

Power factor

50% 75% 100%
0.76  0.84  0.86 
Frame 284T
Output 25 HP (18.5 kW)
Number of Poles 4
Frequency 50 Hz
Rated speed 1460 rpm
Slip 2.67 %
Rated voltage 400 V
Rated current 34.3 A
L. R. Amperes 189 A
LRC 5.5x(Code F)
No load current 11.7 A
Rated torque 89.9 ft.lb
Locked rotor torque 200 %
Breakdown torque 240 %
Locked rotor time 25s (cold) 14s (hot)
Moment of inertia (J) 5.11 sq.ft.lb
Design B
Insulation Class F
Service factor 1.00
Temperature rise 105 K
Duty Cycle Cont.(S1)
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP55
Enclosure IC410 - TEAO
Mounting F-2
Rotation¹ Both (CW and CCW)
Noise level² 61.0 dB(A)
Approx. weight³ 375 lb
(1) Looking the motor from the shaft end.; (2) Measured at 1m and with tolerance of +3dB(A).; (3) Approximate weight, subject to be changed after manufacturing process.; (4) At 100% of full load.

Efficiency

50% 75% 100%
92.4  92.4  91.7 

Power factor

50% 75% 100%
0.73  0.82  0.85 
Frame 284T
Output 25 HP (18.5 kW)
Number of Poles 4
Frequency 50 Hz
Rated speed 1465 rpm
Slip 2.33 %
Rated voltage 415 V
Rated current 33.2 A
L. R. Amperes 196 A
LRC 5.9x(Code G)
No load current 12.4 A
Rated torque 89.6 ft.lb
Locked rotor torque 220 %
Breakdown torque 260 %
Locked rotor time 25s (cold) 14s (hot)
Moment of inertia (J) 5.11 sq.ft.lb
Design B
Insulation Class F
Service factor 1.00
Temperature rise 105 K
Duty Cycle Cont.(S1)
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP55
Enclosure IC410 - TEAO
Mounting F-2
Rotation¹ Both (CW and CCW)
Noise level² 61.0 dB(A)
Approx. weight³ 375 lb
(1) Looking the motor from the shaft end.; (2) Measured at 1m and with tolerance of +3dB(A).; (3) Approximate weight, subject to be changed after manufacturing process.; (4) At 100% of full load.

Efficiency

50% 75% 100%
92.4  92.4  92.4 

Power factor

50% 75% 100%
0.70  0.80  0.84 

Features

Frame Material Cast Iron 
Impregnation Method Double impregnation polyester 
Space Heater Voltage 110-127/200-240 V 
Main terminal box hole NPT 1 1/2" 
Terminal Block Without 
Shaft Locking Device Without 
Drain Rubber, automatic 
Shaft Material SAE 1040/45 Carbon Steel 
Painting RAL 5009 202E (ISO 12944 - C4) 
Grounding Lugs Single 
Fan Cover material Without Fan Cover 
Tropicalized Painting Complete (200h) 
Joints Seal Permatex 
Fan material Without fan 
Bearing cap Yes- Bearing Cap 
Drip Cover Without 
Overload protector (phenolic) Without overload protector  
Connection Cables Quantity 12